Panasonic Mono-Bloc 7kW (R32) J-gen Aquarea outdoor unit

Panasonic Mono-Bloc 7kW (Aquarea J-gen) WH-MDC07J3E5.png
Article number:
WH-MDC07J3E5
  • Delivery time:

The Panasonic Aquarea J-series heat pumps, with a capacity range from 5 to 9 kW, are optimally designed for a wide range of applications, both for new construction and renovation projects. This series uses the environmentally friendly R32 refrigerant, resulting in high energy efficiency and reduced CO2 emissions. A characteristic of the J-series is its robust construction, allowing these heat pumps to operate reliably under various weather conditions.

Don't forget to order matching components
To gain remote access to the heat pump, we recommend ordering the Smart Cloud adapter, which can be found under the 'Related' tab. You will also find matching accessories such as a boiler, buffer tank, sensors, etc.

Request a quote without obligation
If you have a larger project or are unsure about the required products, we kindly request you to ask for a quote from us. This is entirely non-binding. Fill in your details and specific requirements, after which our team will contact you to create a detailed custom quote. This will provide you with all the necessary information to make an informed choice. We have prepared a form to make your request as easy as possible. View it here the quote request form.

Do you have a question or need advice? Our advisors are ready to help
Heat pumps, and related products, are technical and sometimes complex. In addition, each application is unique. 'Difficult situations' for the application of heat pumps can arise in existing buildings or in new construction projects (noise, space, appearance). That's why we're happy to think along with you. Refer to the 'Downloads' section for brochures and other documentation. If your question has not been answered yet, please contact us via phone, email, or the contact form.

Brand Panasonic
Product line Aquarea
Type WH-MDC07J3E5
Component Outdoor unit
Type of heat pump Air/water
Generation J (R32)
T-CAP variant No
Product class (ETIM) EC012035
Configuration Mono-Bloc
Energy label for heating in warm climate (W 35°C / W 55°C) (1) (A+++ to D) A+++ / A+++
Average energy class in heating (W 35°C / W 55°C) (1) (A+++ to D) A+++ / A++
Energy class in heating cold climate (W 35°C / W 55°C) (1) (A+++ to D) A++ / A+
Seasonal energy efficiency in heating in a warm climate (W 35°C / W 55°C) (ns%) 227 / 160 ns%
Average seasonal energy efficiency in heating (W 35°C / W 55°C) (ns%) 193 / 130 ns%
Average seasonal energy efficiency in heating (W 35°C / W 55°C) (SCOP) 4,90 / 3,32 SCOP
Cooling capacity A 35°C / W 7°C 7 kW / 3,06 EER
Cooling Capacity (A 35°C / W 18°C) 8 kW / 4,73 EER
Seasonal energy efficiency in heating in warm climate (W 35°C / W 55°C) (SCOP) 5,75 / 4,07 SCOP
Seasonal energy efficiency for heating in a cold climate (W 35°C / W 55°C) (ns%) 164 / 116 ns%
Seasonal energy efficiency in heating in cold climate (W 35°C / W 55°C) 4,18 / 2,98 SCOP
Sound power level at partial load (heating) (dB(A)) 59 dB(A)
Heating capacity (A -7°C / W 35°C) 6,8 kW / 2,81 COP
Heating capacity (A 7°C / W 55°C) 6,3 kW / 1,86 COP
Heating capacity A +2°C / W 35°C 7 kW / 3,4 COP
Heating capacity (A +2°C / W 55°C) 6,3 kW / 2,16 COP
Heating capacity (A +7°C / W 35°C) 7 kW / 4,76 COP
Heating capacity (A +7°C / W 55°C) 7 kW / 2,82 COP
Power (exact) 7 kW
Sound power level at full load (heating) (dB(A)) 68 dB(A)
Sound power Full load (cooling) (dB(A)) 67 dB(A)
Dimensions (h x w x d) (mm) 865x1283x320 mm
Net weight (kg) 104 kg
Refrigerant amount (kg) 1.3 kg
CO2 equivalent (T) 0.878 T
Connector water piping (inch) 1¼ inch
Pump (number of speeds) Variable speed
Pump (minimum consumed power) (W) 36 W
Pump (maximum consumed 100 W
Water flow for heating (∆T=5 K, 35°C) (L/min) 20.1 L/min
Integrated electric heating capacity (kW) 3 kW
Consumed power 1.47 kW
Power consumption (cooling) (kW) 2.29 kW
Current and starting current (heating) (A) 7 A
Current strength and starting current 10.5 A
Current 1 (A) 17 A
Current 2 (A) 13 A
Recommended indoor fuse (A) 30 / 15 A
Recommended cable size/thickness for delivery 1 (mm2) 3 x 2,5 mm3
Recommended cable size/thickness for delivery 2 (mm2) 3 x 1,5 mm3
Temperature range -20 ~ 35 °C
Temperature range - outside temperature (cooling) (°C) 10 ~ 43 °C
Water outlet (heating) (°C) 20 ~ 60 °C
Water outlet (cooling) (°C) 5 ~ 20 °C
Phases 1 fase